Welcome
წყლის მილი

Single jacket hose

ფასი: 0

Single Jacket Hose

Single jacket fire hose consists of 100% polyester plain-woven single jacket and synthetic rubber and natural rubber lining. This fire hose have very good zto ageing and abrasiveness. The light fire hose is suitable for normal situation. Single jacket hose made of high tenacity polyester staple and polyester filaments. Lining is natural rubber. Jacket is plain. Between the jacket and the rubber tube there is special adhesion.

Fire Fighting Hose (2layers) - Single Jacket

Model No: Diameter(inch) Service Test 
Pressure
(Bar / Psi)
Hydrostatic Strength 
Test Pressure
(Bar / Psi)
Standard
Compliance /
Approvals
NF-FH38 1.5 14 / 200 50 / 725 UL 219,
NFPA 14/
UL listed
NF-FH65 2.5 14 / 200 50 / 725
         
Model No: Diameter(inch) Maximum Working
Pressure(Bar)
Burst Pressure
(Bar)
Manufacturing
Standard
Syntex Series 1.5 / 2 / 2.5 15 50 BS6391: 2009 &
DIN 14811

Features :

  • Manufactured according to BS 6391
  • Outside - synthetic woven textile reinforcement.
  • Inside - High tensile synthetic rubber (Optional material: P.U.).
  • Maintenance free: Do not need drying.
  • Unaffected by Mildew & Rot proof.
  • Abrasion resistance due to synthetic coating.
  • Excellent resistance to Ozone.

Specifications:

  • Available colours: White & Red
  • Standard lengths: 75ft, 100ft,200ft, Other lengths available upon request.

SINGLE JACKET HOSE, Type 2

Single jacket fire hose consists of an Impermeable Elastomeric Lining, a synthetic Fibre Reinforcement
and Externally Applied Elastomeric coating to the Reinforcement.Delivery Hose are non-percolating lay
flat type used in fire fighting purpose. Hose are suitable for use with couplings with the requirements 
of BS 336: 1989 standards. Hose intended for use at working pressure not exceeding15 bar. Delivery
hose are manufactured to comply BS 6391: 2009 Standards.

Features :

  • BSI KITE MARK & LPCB Certified.
  • Light weight and flexible.
  • Hose belongs to Type 2 with Elastomeric lining, Synthetic fiber reinforcement and elastomeric coating on the reinforcement.
  • Hose give good protection against the absorption of liquids and resistance of the reinforcement.
  • Anti rot and anti twist.
  • Hose with couplings are bound by Galvanized mild steel / SS wire.

Specifications:

Hose : Type 2
Availabel Colour : Red, White
Standard Length : 25 / 30 Mtrs

Fire Fighting Hose (2layers) - Single Jacket

Model No: Diameter(inch) Working Pressure
(Bar/Psi)
Burst Pressure
(Bar / Psi)
Standard
Compliance /
Approvals
NF-DH2-65R 2.5 15 / 215 50 / 725 BS 6391: 2009 /
Kite Mark & LPCB
NF-DH2-65W

Applications:

  • Industrial and rural fire brigades as well as building protection.